
UNDERFLOOR
HEATING FOR COLD TILED FLOORS
Tile
and stone floors in bathrooms, hallways and kitchens don't have
to be cold to the touch any more. New technology has made it
possible to develop a heating cable which is fairly small in
diameter. Together with the grout, this raises the thickness
of the floor by about 10mm. Heating cable diameter is approximately
6mm and is overbraided with tin platted copper to reduce EMF
to negligible levels. This heating cable provides even heat
distribution and installation is very simple.
Heating
cable is insulated with high quality silicone rubber (suitable
for applications between -60 deg. C and +250 deg.C). All heating
cable units are fully factory terminated with 3 metre cold leads.
All the installer needs to do is lay the cable onto the floor
in loops by spacing evenly and then connect to the temperature
controller.
We
shall recomend a heating cable unit to match the square metres
of floor area you need to heat. Usually 60 watts per square
metre is required in houses which are newly built or have supplementary
insulation, 80 watts per square metre in houses which are older.
Power supply should be 230V ac. Heating cable output is 10 watts
/ metre.

Application
Methods




Underfloor
Heating Systems Installation Testing
Heating cable should be tested with a 500V DC insulation tester,
for insulation and continuity, prior to cable laying. The insulation
resistance should not be less than 100 mega ohms. This test
should be repeated again after laying the cable.
Installation
Clear surface free from debris. It is essential to sweep the
floor before laying commences to remove any sharp objects which
might damage the cable. Fix welded wire mesh (usually 1mm sq.
O.D. wire welded into 15mm squares) to the concrete base by
using hardened nails, where waterproof membrane is used dabs
of hot bitumen can be applied. Now determine the starting point
on the plan ensuring both cold tails return to this point, allowing
for the cold tail connections. Lay the cable in accordance with
the recomended pitch to achieve the watts/metre square required
for a particular application. Heating cable should not touch
or cross, or be in direct contact with any insulation material.
Cold tail/heating joints should be spaced at least 50mm apart
and buried in the concrete floor. Tie the cable to the wire
mesh at every 20cm using cable ties. Cable runs may be transverse
or longitudinal onto a flat surface, but when steps are involved,
transverse runs should be used with the cable dropping down
the riser to each lower step. A fine concrete screed should
be used for surfacing and may be finished with a continuous
layer of asphalt to provide a smooth surface.
Control
For small installations an air sensing or surface sensing stat
is sufficient to energise the system when the temperature drops
below a set point.
For
larger installations a more advanced control system may be desirable.
So that a low surface temperature does not call for underfloor
heating until moisture is deposited upon the surface which would
result in freezing. For economy in operation, therefore, providing
the surface remains dry, heat is withheld until the surface
arrives at, or even falls slightly below, freezing point. Consequently,
temperature control is linked with detectors which detect the
presence of moisture and of snow. A moisture detector consists
of a pair of electrodes placed at surface level, a signal being
initiated by the fall of resistance between them which occurs
when moisture is present. The detector for snow contains a heater
which melts the snow in order to gain the same effect.